CB-7011/CB-7011D, CD-7018 Users Manual
2.38 ~AA5PPSS
Description: Set PowerOn Value and Safe Value.
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: ~AA5PPSS[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
5 command for setting PowerOn Value and Safe Value
PP PowerOn Value, 00=DO0 off, DO1 off, 01=DO0 on,
DO1off, 02=DO0 off, DO1 on, 03=DO0 on, DO1 on
SS Safe Value, data format is same as PP
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: ~0150003 Receive: !01
Set address 01 PowerOn Value is DO0 off, DO1 off, Safe
Value is DO0 on, DO1 on, return success.
Related Command:
Sec. 2.37 ~AA4
Related Topic:
Sec. 3.2 Module Status, Sec. 3.3 Dual Watchdog Operation