1.10 Configuration Tables
Configuration Table of CB-7011/11D/11P/11PD/18/18P:
Baud rate Setting (CC)
Analog Input Type Setting (TT)
T.C. Type L and M for CB-7011P/11PD/18P only.
Data Format Setting (FF)
*1: Filter Select: 0 = 60 Hz rejection
1 = 50 Hz rejection
*2: Checksum Bit: 0=Disable, 1=Enable
*3: 00 = Engineering Unit Format
01 = Percent Format
10 = 2’s Complement HEX Format
edoC30405060708090A0
etarduaB0021004200840069002910048300675002511
76543210
1*2* 0000 3*
edoCepyT00102030405060
tupnI.niMVm51-Vm05-Vm001-Vm005-V1-V5.2-Am02-
tupnIxaMVm51+Vm05+Vm001+Vm005+V1+V5.2+Am02+
Type Code 0E 0F 10 11 12 13 14 15 16 17 18
TC Type J K T E R S B N C L M
Min Temp 0 -200 -200 -200 0 0 0 -270 0 -200 -200
Max Temp 750 1250 350 900 1450 1450 1700 1300 2320 800 100
The temperatures shown are in degrees Celsius.