CB-7011/CB-7011D, CB-7018 Users Manual
2.4 #AAN
Description: Read Analog Input from channel N
Note: The command is for CB-7018/18P only.
Syntax: #AAN[CHK](cr)
# delimiter character
AA address of reading module (00 to FF)
N channel to read, from 0 to 7
Response: Valid Command: >(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
> delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
(Data) analog input value, reference Sec. 1.10 for its format
Example:
Command: #032 Receive: >+02.513
Read address 03 channel 2, get data success.
Command: #029 Receive: ?02
Read address 02 channel 9, return error channel number.
Related Command:
%AANNTTCCFF (Sec. 2.1), $AA2 (Sec 2.7)