40
CB-7011/CB-7011D, CD-7018 User’s Manual
2.19 ~AAO(Data)
Description: Set Module Name
Syntax: ~AAO(Data)[CHK](cr)
~ delimiter character
AA address of setting module (00 to FF)
O command for setting module name
(Data) new name for module, max 6 characters
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no
response.
! delimiter for valid command
? delimiter for invalid command
AA address of response module(00 to FF)
Example:
Command: ~01O7018 Receive: !01
Set address 01 module name to 7018, return success.
Command: $01M Receive: !017018
Read address 01 module name, return 7018.
Related Command:
$AAM (Sec. 2.17)
Comentarios a estos manuales