51
CB-7011/CB-7011D, CB-7018 User’s Manual
2.29 @AARL
Description: Read Low Alarm
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: @AARH[CHK](cr)
@ delimiter character
AA address of reading module (00 to FF)
RL command for reading low alarm
Response: Valid Command: !AA(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax error or communication error may get no re-
sponse.
! delimiter for valid command.
? delimiter for invalid command.
AA address of response module(00 to FF)
(Data) low alarm value in engineer unit format.
Example:
Command: @01RL Receive: !01-2.5000
Read address 01 low alarm, return -2.5000.
Related Command:
Sec. 2.25 @AALO(Data)
Related Topic:
Sec. 3.6 High/Low Alarm