Measurement-computing CB-7011 Manual de usuario Pagina 24

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 23
24
CB-7011/CB-7011D, CD-7018 Users Manual
2.3 #AA
Description: Read Analog Input
Syntax: #AA[CHK](cr)
# delimiter character
AA address of reading module(00 to FF)
Response: Valid Command: >(Data)[CHK](cr)
Syntax error or communication error may yield no re-
sponse.
> delimiter for valid command
(Data) analog input value, reference Sec. 1.10 for its format.
For CB-7018/18P, the data is the combination for each chan-
nel respectively.
Example:
Command: #01 Receive: >+02.635
Read address 01, return data success.
Command: #02 Receive: >4C53
Read address 02, return data in HEX format success.
Command: #04
Receive: >+05.123+04.153+07.234-02.356+10.000-
05.133+02.345+08.234
Module address 04 is CB-7018. Read address 04, get analog
input data of eight channels.
Related Command:
%AANNTTCCFF (Sec. 2.1), $AA2 (Sec. 2.7)
Related Topics:
Configuration Tables (Sec. 1.10)
Vista de pagina 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 67 68

Comentarios a estos manuales

Sin comentarios