23
CB-7011/CB-7011D, CB-7018 Users Manual
2.2 #**
Description: Synchronized Sampling
Note: The command is for CB-7011/11D/11P/11PD only.
Syntax: #**[CHK](cr)
# a delimiter character
** synchronized sampling command
Response: No response
Example:
Command: $014 Receive: ?01
Read synchronized sampling data, returns no valid data .
Command: #** No response
Send synchronized sampling command.
Command: $014 Receive: >011+025.123
First read, get status=1, first read.
Command: $014 Receive: >010+025.123
Second read, get status=0, read verified.