CB-7080 & CB-7080D Counter/Timer User's Guide @AADA
2-42
@AADA
Description: Disable alarm (for alarm-mode 1). Refer to "Counter alarm mode selection" for more
information.
Syntax: @AADA[chk](cr)
@ A delimiter character
AA 2-character HEX module address, from 00 to FF
DA
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response !AA[chk](cr)
Invalid response ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Examples:
Disable the alarm for module 1:
command: @01DA(cr)
response: !01(cr)
Disable the alarm for module 2:
command: @02DA(cr)
response: !02(cr)