CB-7080 & CB-7080D Counter/Timer User's Guide $AAM
2-35
$AAM
Description: Read the module name.
Syntax: $AAM[chk](cr)
$ A delimiter character
AA 2-character HEX module address, from 00 to FF
M
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Response:
Valid response !AA(data)[chk](cr)
Invalid response ?AA[chk](cr)
no response Syntax error, communication error or address error
! A delimiter character indicating a valid response
? A delimiter character indicating an invalid response
AA 2-character HEX module address
data 4-character for module name
[chk] 2-character checksum. If checksum is disabled, no [chk]
(cr) 0x0D
Examples:
Module name of 01 is 7080:
command: $01M(cr)
response: !017080(cr)
Module name of 02 is 7080D:
command: $02M(cr)
response: !027080D(cr)