CB-7012, CB-7014, CB-7017 Users Manual
2.25 @AACA
Description: Clear Latch Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AACA[CHK](cr)
@ Delimiter character
AA Address of module to set (00 to FF)
CA Command for clear latch alarm
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: @01DI Receive: !0120101
Read Address 01 digital input, return latch alarm mode, low
alarm active.
Command: @01CA Receive: !01
Clear Address 01 latch alarm, return successful.
Command: @01DI Receive: !0120001
Read Address 01 digital input, return latch alarm mode, no
alarm active.
Related Command:
Sec. 2.19, @AADI; Sec. 2.21, @AAEAT; Sec. 2.24, @AADA