CB-7012, CB-7014, CB-7017 Users Manual
2.23 @AALO(Data)
Description: Set Low Alarm
Note: This command is for CB-7012/12D/12F/12FD/14D only.
Syntax: @AALO(Data)[CHK](cr)
@ Delimiter character
AA Address of module to set (00 to FF)
LO Command for setting low alarm value
(Data) low alarm values, data format is in engineering units.
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
Example:
Command: @01LO-10.000 Receive: !01
Set Address 01 low alarm -10.000; return successful.
Related Command:
Sec. 2.21, @AAEAT; Sec. 2.27, @AARL
Related Topic:
Sec. 3.6, High/Low Alarm