CB-7012, CB-7014, CB-7017 Users Manual
2.4 #AAN
Description: Read Analog Input from channel N
Note: This command is for CB-7017/17F only.
Syntax: #AAN[CHK](cr)
# Delimiter character
AA Address for module (00 to FF)
N channel to read, from 0 to 7
Response: Valid Command: >(Data)[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
> Delimiter for valid command
? Delimiter for invalid command
AA Address of responding module (00 to FF)
(Data) analog input value; see Sec. 1.10 for its format
Example:
Command: #032 Receive: >+02.513
Read Address 03 channel 2, get data successfully.
Command: #029 Receive: ?02
Read Address 02 channel 9, return error channel number.
Related Command:
Sec. 2.1 %AANNTTCCFF, Sec. 2.7 $AA2
Related Topics:
Sec. 1.10 Configuration Tables