CB-7021, CB-7022, CB-7024 Users Manual
CB-7024 Current Output Calibration Sequence:
1. Connect meter to module’s voltage output channel 0.
2. Warm-Up for 30 minutes.
3. Setting type to 33. (10 to 10V) -> Refer Sec. 2.1.
4. Output 10V. -> Refer Sec. 2.15.
5. Check the meter and trim the output for
10V match by using trim command. -> Refer Sec. 2.18.
6. Perform 10V Calibration Command. -> Refer Sec. 2.16.
7. Program output for 10V. Refer Sec. 2.15.
8. Check the meter and trim the output for
10V match by using trim command.-> Refer
Sec. 2.18.
9. Perform 10V Calibration Command. -> Refer Sec. 2.17.
10. Repeat 1 to 9 for channel 1, 2 and 3.