CB-7021, CB-7022, CB-7024 User’s Manual
2.32 ~AA5
Description: Set Safe Value.
Note: The command is for CB-7021/21P only.
Command: ~AA5[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
5 Command to store current output as Safe Value
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may not get a response.
! Delimiter for valid command
? Delimiter for invalid command
AA Address of response module (00 to FF)
Example:
Command: #0100.000 Receive: !01
Output address 01 value 0.0, returns successful.
Command: ~015 Receive: !01
Set address 01 Safe Value, returns successful.
Related Command:
Sec. 2.25, ~**; Sec. 2.26, ~AA0; Sec. 2.27, ~AA1; Sec. 2.28, ~AA2;
Sec. 2.29, ~AA3EVV; Sec. 2.30, ~AA4
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation