2.19 ~AA1
Description: Reset Module Status
Command: ~AA1[CHK](cr)
~ Delimiter character
AA Address of setting module (00 to FF)
1 Command for reset module status
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module (00 to FF)
Example:
Refer to Sec. 2.21, ~AA3EVV example.
Related Command:
Sec. 2.17, ~**; Sec. 2.18, ~AA0; Sec. 2.20, ~AA2; Sec. 2.21,
~AA3EVV; Sec. 2.22, ~AA4V; Sec. 2.23, ~AA5V
Related Topic:
Sec. 3.2, Module Status; Sec. 3.3, Dual Watchdog Operation