CB-7000 DIO Manual
2.1 %AANNTTCCFF
Description: Set module Configuration
Syntax: %AANNTTCCFF[CHK](cr)
% Delimiter character
AA Address of setting module (00 to FF)
NN New Address for setting module (00 to FF)
TT Type 40 for DIO module
CC New baud rate for setting module (Ref. Sec. 1.9). Short
INIT* to ground when changing baud rate. (Ref Sec. 3.1)
FF New data format for setting module (Ref. Sec. 1.9). Short
the INIT* to ground to change checksum setting. (Ref.
Sec. 3.1)
Response: Valid Command: !AA[CHK](cr)
Invalid Command: ?AA[CHK](cr)
Syntax or communication error may get no response.
! Delimiter for valid Command
? Delimiter for invalid Command
AA Address of response module(00 to FF)
Example:
Command: %0102400600 Receive: !02
Set module Address 01 to 02; return successful.