Remote I/O Configuration, General Tab
(e) Fill in the “Define RS-485 Communications for this Station” fields in the RS-485 tab, then click
<Next>. See following figure.
Information in the following figure [Remote I/O Configuration, RS-485 tab] refers to the RS-485 port
on the “RS-485 connected” module.
Protocol -
- For a /100 Series Module: Select <ModBus ASCII Slave>
- For a /200 Series module: Select <Modbus ASCII>.
Baud Rate - Needs to match the baud rate of the RS-485 link on the “Ethernet-
connected” /100 series module to which it is connected.
Mode, Lead Time, Lag Time - Accept the defaults. Click <Help> for more information.
Remote I/O Configuration, RS-485 Tab
14 878395 PointScan Road Map