5-2 Analog Input Modules
9-12-01
PointScan/200 Users Manual
PointScan/242
High Density Discrete Output Module
Overview
Sixteen discrete outputs provide power for loads up to 1 Amp. This module does not provide over current
protection or TPO capabilities. More information can be found in the on-line help supplied with the IO
Toolkit.
Number of Channels 16 discrete outputs connected to a common DC source
Output Voltage Range 10 - 30 VDC
Max. Load per Output 1 Amp
Max. Load per Module 10 Amps
Max. Inrush Current 5 Amps (for 100 mS)
Wiring
A single terminal is provided for each output channel. All outputs are powered from the DC power
terminal. All channels are referenced to a common return which is connected to the negative side (ground)
of the DC power source.
I/O Registers
Function IOtech Registers Modbus Registers
Discrete Outputs Y0 - Y15 00001 - 00016